Description
Currently these two classes are defined as:
Leaving_Chilled_Water_Temperature_Sensor : Measures the temperature of chilled water that is supplied from a chiller
Entering_Chilled_Water_Temperature_Sensor : Measures the temperature of chilled water that is enteringed to a cooling tower
I have several concerns and would like to get consensus before creating a pull request.
- Entering_Chilled_Water_Temperature_Sensor is not the temperature of the water entering the cooling tower. That would be condenser water.
- I don't know that these definitions should refer to the chiller. I think that perhaps they should be like Entering_Chilled_Water_Flow_Sensor that doesn't refer to the chiller, but just refers to "chilled entering water" (although I would prefer "entering chilled water").
- How would these be used outside of a chiller? If a water cooled AHU has a point measuring the temperature of it's incoming chilled water, it would seem to be the Entering_Chilled_Water_Temperature_Sensor, but by the above definitions, it should probably be the Leaving one since that is defined as what is supplied by the chiller. I think that having the chiller as part of the definition is confusing.
- Lastly - I don't think that there is a clear way of distinguishing the chilled water leaving a specific chiller from the chilled water leaving the whole chiller plant. This was brought up in Issue 628, but doesn't seem to be resolved.
I am proposing:
Leaving_Chilled_Water_Temperature_Sensor : Measures the temperature of chilled water that is leaving an equipment
Entering_Chilled_Water_Temperature_Sensor : Measures the temperature of chilled water that is entering an equipment
To me this would mean that the a point in an AHU measuring the temperature of it's incoming chilled water would be an Entering_Chilled_Water_Temperature_Sensor.
I'm not clear how to model the chilled water for the whole chiller plant. Would this be a Leaving_Chilled_Water_Temperature_Sensor on a Chilled_Water_System?