@@ -125,6 +125,8 @@ OAFC:
125
125
- economizer_mode
126
126
- mixed_air_temperature_sensor
127
127
- failed_mixed_air_temperature_alarm
128
+ - high_mixed_air_temperature_alarm
129
+ - low_mixed_air_temperature_alarm
128
130
uses :
129
131
- outside_air_damper_percentage_command
130
132
- outside_air_flowrate_sensor
@@ -321,6 +323,7 @@ CO2C:
321
323
- zone_air_co2_concentration_setpoint
322
324
opt_uses :
323
325
- high_zone_air_co2_concentration_alarm
326
+ - failed_zone_air_co2_concentration_alarm
324
327
325
328
326
329
CO2CDSP :
@@ -335,6 +338,7 @@ CO2CDSP:
335
338
- zone_air_co2_concentration_sensor
336
339
opt_uses :
337
340
- high_zone_air_co2_concentration_alarm
341
+ - failed_zone_air_co2_concentration_alarm
338
342
339
343
340
344
COC :
@@ -723,6 +727,7 @@ SSPC:
723
727
- supply_fan_speed_frequency_sensor
724
728
- supply_fan_speed_percentage_command
725
729
- failed_supply_fan_alarm
730
+ - failed_supply_air_static_pressure_alarm
726
731
- high_supply_air_static_pressure_alarm
727
732
- low_supply_air_static_pressure_alarm
728
733
uses :
@@ -1217,6 +1222,7 @@ SCHWTC:
1217
1222
- cooling_request_count
1218
1223
- cooling_run_command
1219
1224
- failed_cooling_alarm
1225
+ - failed_chilled_supply_water_temperature_alarm
1220
1226
- high_chilled_supply_water_temperature_alarm
1221
1227
- low_chilled_supply_water_temperature_alarm
1222
1228
uses :
@@ -1251,6 +1257,9 @@ RCHWTC:
1251
1257
- chilled_supply_water_temperature_sensor
1252
1258
- cooling_percentage_command
1253
1259
- cooling_request_count
1260
+ - failed_chilled_return_water_temperature_alarm
1261
+ - high_chilled_return_water_temperature_alarm
1262
+ - low_chilled_return_water_temperature_alarm
1254
1263
uses :
1255
1264
- chilled_return_water_temperature_sensor
1256
1265
- chilled_return_water_temperature_setpoint
@@ -1384,6 +1393,8 @@ MTM:
1384
1393
- mixed_air_dewpoint_temperature_sensor
1385
1394
- mixed_air_relative_humidity_sensor
1386
1395
- failed_mixed_air_temperature_alarm
1396
+ - high_mixed_air_temperature_alarm
1397
+ - low_mixed_air_temperature_alarm
1387
1398
uses :
1388
1399
- mixed_air_temperature_sensor
1389
1400
implements :
@@ -1401,6 +1412,8 @@ MTC:
1401
1412
- OPERATIONAL
1402
1413
opt_uses :
1403
1414
- failed_mixed_air_temperature_alarm
1415
+ - high_mixed_air_temperature_alarm
1416
+ - low_mixed_air_temperature_alarm
1404
1417
1405
1418
1406
1419
STM :
@@ -1636,6 +1649,7 @@ CO2M:
1636
1649
- MONITORING
1637
1650
opt_uses :
1638
1651
- high_zone_air_co2_concentration_alarm
1652
+ - failed_zone_air_co2_concentration_alarm
1639
1653
1640
1654
1641
1655
VOCM :
@@ -1754,6 +1768,7 @@ SSPM:
1754
1768
implements :
1755
1769
- MONITORING
1756
1770
opt_uses :
1771
+ - failed_supply_air_static_pressure_alarm
1757
1772
- high_supply_air_static_pressure_alarm
1758
1773
- low_supply_air_static_pressure_alarm
1759
1774
@@ -3394,6 +3409,8 @@ ECON:
3394
3409
- return_air_damper_percentage_command
3395
3410
- supply_air_temperature_sensor
3396
3411
- failed_mixed_air_temperature_alarm
3412
+ - high_mixed_air_temperature_alarm
3413
+ - low_mixed_air_temperature_alarm
3397
3414
- high_return_air_temperature_alarm
3398
3415
- high_supply_air_temperature_alarm
3399
3416
- low_return_air_temperature_alarm
@@ -3423,6 +3440,8 @@ ECOND:
3423
3440
- return_air_temperature_sensor
3424
3441
- failed_discharge_air_temperature_alarm
3425
3442
- failed_mixed_air_temperature_alarm
3443
+ - high_mixed_air_temperature_alarm
3444
+ - low_mixed_air_temperature_alarm
3426
3445
- high_return_air_temperature_alarm
3427
3446
- low_return_air_temperature_alarm
3428
3447
uses :
@@ -3447,6 +3466,8 @@ ECONM:
3447
3466
- return_air_damper_percentage_command
3448
3467
- supply_air_temperature_sensor
3449
3468
- failed_mixed_air_temperature_alarm
3469
+ - high_mixed_air_temperature_alarm
3470
+ - low_mixed_air_temperature_alarm
3450
3471
- high_return_air_temperature_alarm
3451
3472
- high_supply_air_temperature_alarm
3452
3473
- low_return_air_temperature_alarm
@@ -3479,6 +3500,10 @@ ECONM2X:
3479
3500
- average_mixed_air_temperature_sensor
3480
3501
- failed_mixed_air_temperature_alarm_1
3481
3502
- failed_mixed_air_temperature_alarm_2
3503
+ - high_mixed_air_temperature_alarm_1
3504
+ - low_mixed_air_temperature_alarm_1
3505
+ - high_mixed_air_temperature_alarm_2
3506
+ - low_mixed_air_temperature_alarm_2
3482
3507
uses :
3483
3508
- economizer_mode
3484
3509
- mixed_air_temperature_sensor_1
@@ -3505,6 +3530,8 @@ ECONMD:
3505
3530
- return_air_temperature_sensor
3506
3531
- failed_discharge_air_temperature_alarm
3507
3532
- failed_mixed_air_temperature_alarm
3533
+ - high_mixed_air_temperature_alarm
3534
+ - low_mixed_air_temperature_alarm
3508
3535
- high_return_air_temperature_alarm
3509
3536
- low_return_air_temperature_alarm
3510
3537
uses :
@@ -3533,6 +3560,8 @@ ECONZ:
3533
3560
- return_air_temperature_sensor
3534
3561
- failed_discharge_air_temperature_alarm
3535
3562
- failed_mixed_air_temperature_alarm
3563
+ - high_mixed_air_temperature_alarm
3564
+ - low_mixed_air_temperature_alarm
3536
3565
- failed_zone_air_temperature_alarm
3537
3566
- high_return_air_temperature_alarm
3538
3567
- high_zone_air_temperature_alarm
@@ -3558,6 +3587,8 @@ VOADM:
3558
3587
- mixed_air_temperature_sensor
3559
3588
- outside_air_damper_percentage_sensor
3560
3589
- failed_mixed_air_temperature_alarm
3590
+ - high_mixed_air_temperature_alarm
3591
+ - low_mixed_air_temperature_alarm
3561
3592
- failed_outside_air_damper_alarm
3562
3593
uses :
3563
3594
- outside_air_damper_percentage_command
@@ -3598,6 +3629,8 @@ OAFMC:
3598
3629
- economizer_mode
3599
3630
- mixed_air_temperature_sensor
3600
3631
- failed_mixed_air_temperature_alarm
3632
+ - high_mixed_air_temperature_alarm
3633
+ - low_mixed_air_temperature_alarm
3601
3634
- ventilation_request_count
3602
3635
uses :
3603
3636
- outside_air_damper_percentage_command
@@ -4522,6 +4555,7 @@ BYPSSPC:
4522
4555
opt_uses :
4523
4556
- supply_air_flowrate_sensor
4524
4557
- failed_supply_fan_alarm
4558
+ - failed_supply_air_static_pressure_alarm
4525
4559
- high_supply_air_static_pressure_alarm
4526
4560
- low_supply_air_static_pressure_alarm
4527
4561
uses :
@@ -4541,6 +4575,7 @@ BYPSSPC2X: # Consider virtual point for instances where dampers control to same
4541
4575
opt_uses :
4542
4576
- supply_air_flowrate_sensor
4543
4577
- failed_supply_fan_alarm
4578
+ - failed_supply_air_static_pressure_alarm
4544
4579
- high_supply_air_static_pressure_alarm
4545
4580
- low_supply_air_static_pressure_alarm
4546
4581
uses :
@@ -4982,6 +5017,7 @@ SDBPC:
4982
5017
is_abstract : true
4983
5018
opt_uses :
4984
5019
- supply_air_flowrate_sensor
5020
+ - failed_supply_air_static_pressure_alarm
4985
5021
- high_supply_air_static_pressure_alarm
4986
5022
- low_supply_air_static_pressure_alarm
4987
5023
uses :
@@ -6003,6 +6039,7 @@ CO2DFVSC:
6003
6039
- CONTROL
6004
6040
opt_uses :
6005
6041
- high_zone_air_co2_concentration_alarm
6042
+ - failed_zone_air_co2_concentration_alarm
6006
6043
6007
6044
6008
6045
CO2EFVSC :
@@ -6012,6 +6049,7 @@ CO2EFVSC:
6012
6049
opt_uses :
6013
6050
- exhaust_fan_speed_percentage_sensor
6014
6051
- high_zone_air_co2_concentration_alarm
6052
+ - failed_zone_air_co2_concentration_alarm
6015
6053
uses :
6016
6054
- exhaust_fan_speed_percentage_command
6017
6055
- zone_air_co2_concentration_sensor
@@ -6165,6 +6203,8 @@ VOADM2X:
6165
6203
- outside_air_flowrate_sensor_1
6166
6204
- outside_air_flowrate_sensor_2
6167
6205
- failed_mixed_air_temperature_alarm
6206
+ - high_mixed_air_temperature_alarm
6207
+ - low_mixed_air_temperature_alarm
6168
6208
uses :
6169
6209
- outside_air_damper_percentage_command_1
6170
6210
- outside_air_damper_percentage_command_2