What to Validate

Coefficients b1, b2, b3 for Equations (14)-(15).

IEEE 1584-2018 Reference

  • Section: 4.8.4
  • Table: 7 (page ~31)

Current Implementation

  • File: arc_flash_studio/ieee1584/tables.py
  • Variables:
    • TABLE_7_ENCLOSURE_TYPICAL
    • TABLE_7_ENCLOSURE_SHALLOW

Acceptance Criteria

  • Typical enclosure: VCB, VCBB, HCB coefficients match
  • Shallow enclosure: VCB, VCBB, HCB coefficients match
  • VOA/HOA have b3=1.0 (CF always equals 1)