What to Validate
Complete calculation against IEEE 1584-2018 Annex D.1 worked example.
IEEE 1584-2018 Reference
- Annex D.1 (pages ~58-62)
Test Inputs (from D.1-D.7)
- Ibf = 15 kA
- Voc = 4.16 kV
- Gap = 104 mm
- Working distance = 914.4 mm (36")
- Arc duration = 197 ms
- Enclosure = 508mm × 508mm × 508mm (20" cube)
- Config = VCB
Expected Results (fill in from Annex D)
- Iarc_600 = ___ kA (D.8)
- Iarc_2700 = ___ kA (D.11)
- Iarc_14300 = ___ kA (D.14)
- Final Iarc = ___ kA (D.17)
- VarCf = ___ (D.18)
- Iarc_min = ___ kA (D.19)
- CF = ___ (D.22)
- E_600 = ___ J/cm² (D.24)
- E_2700 = ___ J/cm² (D.26)
- E_14300 = ___ J/cm² (D.28)
- Final E = ___ J/cm² (D.32)
- AFB = ___ mm (D.39)
Acceptance Criteria
- All intermediate values match within 1%
- Final values match within 1%
- Test added to
tests/test_ieee1584.py